All rights reserved.
*/
/* ========================================================================== */
/*
Redistribution and use in source and binary forms, with or without
modification, are permitted provided that the following conditions are met:
1. Redistributions of source code must retain the above copyright notice,
this list of conditions and the following disclaimer.
2. Redistributions in binary form must reproduce the above copyright
notice, this list of conditions and the following disclaimer in the
documentation and/or other materials provided with the distribution.
THIS SOFTWARE IS PROVIDED ``AS IS'' AND ANY EXPRESS OR IMPLIED WARRANTIES,
INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE
AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY,
OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)
ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE
POSSIBILITY OF SUCH DAMAGE.
*/
/* ========================================================================== */
]]>
ApcupsdServices: Apcupsd (General)Monitoring0.2/usr/local/pkg/apcupsd.incApcupsd has been created/modified.Apcupsd has been deleted./usr/local/etc/rc.d/apcupsd.sh restarthttp://www.pfsense.org/packages/config/apcupsd/apcupsd.inc/usr/local/pkg/0755http://www.pfsense.org/packages/config/apcupsd/apcupsd_status.php/usr/local/www/0755http://www.pfsense.org/packages/config/apcupsd/apcupsd.conf.php/usr/local/pkg/0755http://www.pfsense.org/packages/config/apcupsd/apcupsd_mail.php/usr/local/pkg/0755apcupsdapcupsd.shapcupsdApcupsd a daemon for controlling APC UPSesGeneral/pkg_edit.php?xml=apcupsd.xml&id=0Statusapcupsd_status.phpGeneral configuration parameterslisttopicEnableapcupsdenabledEnable APC UPS Daemon servicecheckboxUPS NameupsnameUse this to give your UPS a name in log files and suchinput60trueUPS Cableupscable
Possible generic choices for are:
simple, smart, ether, usb
Or a specific cable model number may be used:
940-0119A, 940-0127A, 940-0128A, 940-0020B,
940-0020C, 940-0023A, 940-0024B, 940-0024C,
940-1524C, 940-0024G, 940-0095A, 940-0095B,
940-0095C, M-04-02-2000
]]>input60trueUPS Type / Deviceupstype
UPSTYPE DEVICE Description
apcsmart /dev/tty** Newer serial character device, appropriate for
SmartUPS models using a serial cable (not USB).
usb BLANK Most new UPSes are USB. A blank DEVICE
setting enables autodetection, which is
the best choice for most installations.
net hostname:port Network link to a master apcupsd through apcupsd's
Network Information Server. This is used if the
UPS powering your computer is connected to a
different computer for monitoring.
snmp hostname:port:vendor:community
SNMP network link to an SNMP-enabled UPS device.
Hostname is the ip address or hostname of the UPS
on the network. Vendor can be can be "APC" or
"APC_NOTRAP". "APC_NOTRAP" will disable SNMP trap
catching; you usually want "APC". Port is usually
161. Community is usually "private".
dumb /dev/tty** Old serial character device for use with
simple-signaling UPSes.
pcnet ipaddr:username:passphrase:port
PowerChute Network Shutdown protocol which can be
used as an alternative to SNMP with the AP9617
family of smart slot cards. ipaddr is the IP
address of the UPS management card. username and
passphrase are the credentials for which the card
has been configured. port is the port number on
which to listen for messages from the UPS, normally
3052. If this parameter is empty or missing, the
default of 3052 will be used.
]]>input60trueDevicedeviceinput60Poll TimepolltimeInterval (in seconds) at which apcupsd polls the UPS for status. Default is 60input1060Kill on Power FailkillonpowerfailHibernate UPS on powerfailcheckboxConfiguration parameters used during power failureslisttopicOnBattery DelayonbatterydelayTime in seconds from when a power failure is detected until we react to it with an onbattery event. Default is 6input106Battery LevelbatterylevelIf during a power failure, the remaining battery percentage (as reported by the UPS) is
below or equal to BATTERYLEVEL, apcupsd will initiate a system shutdown. Default is 5input105MinutesminutesIf during a power failure, the remaining runtime in minutes (as calculated internally
by the UPS) is below or equal to MINUTES, apcupsd, will initiate a system shutdown. Default is 3input103TimeouttimeoutIf during a power failure, the UPS has run on batteries for TIMEOUT many seconds
or longer, apcupsd will initiate a system shutdown. A value of 0 (default) disables this timerinput100AnnoyannoyTime in seconds between annoying users to signoff prior to system shutdown. 0 disables. Default is 300input10300Annoy DelayannoydelayInitial delay after power failure before warning users to get off the system. Default is 60input1060Kill DelaykilldelayIf KILLDELAY is non-zero, apcupsd will continue running after a shutdown has been
requested, and after the specified time in seconds attempt to kill the power. This is for use
on systems where apcupsd cannot regain control after a shutdown. 0 disables (default)input100Configuration statements for Network Information ServerlisttopicNet ServernetserverIf netstatus is on, a network information server process will be started for serving
the STATUS and EVENT data over the network (used by CGI programs)selectonNIS IpnisipIP address on which NIS server will listen for incoming connections. Default value is
0.0.0.0 which means any incoming request will be serviced. Alternatively, you can configure this
setting to any specific IP address of your server and NIS will listen for connections only on that
interface. Use the loopback address (127.0.0.1) to accept connections only from the local machineinput100.0.0.0NIS PortnisportPort to use for sending STATUS and EVENTS data over the network.
It is not used unless NETSERVER is on. If you change this port,
you will need to change the corresponding value in the cgi directory
and rebuild the cgi programs. Default is 3551 as registered with the IANAinput103551Configuration statements used if sharinglisttopicUPS ClassupsclassNormally standalone unless you share an UPS using an APC ShareUPS cardselectstandaloneUPS ModeupsmodeNormally disable unless you share an UPS using an APC ShareUPS cardselectdisablephp_install_apcupsd();validate_input_apcupsd($_POST, &$input_errors);sync_package_apcupsd();php_deinstall_apcupsd();