New package Apcupsd. A daemon for controlling APC UPSes.
Diffstat (limited to 'config/apcupsd/apcupsd.conf.php')
-rw-r--r--config/apcupsd/apcupsd.conf.php362
1 files changed, 362 insertions, 0 deletions
diff --git a/config/apcupsd/apcupsd.conf.php b/config/apcupsd/apcupsd.conf.php
new file mode 100644
index 00000000..6a19b915
--- /dev/null
+++ b/config/apcupsd/apcupsd.conf.php
@@ -0,0 +1,362 @@
+<?php
+/*
+ apcupsd.conf.php
+ part of the apcupsd package for pfSense
+ Copyright (C) 2013 Danilo G. Baio <dbaio@bsd.com.br>
+ All rights reserved.
+
+ Redistribution and use in source and binary forms, with or without
+ modification, are permitted provided that the following conditions are met:
+
+ 1. Redistributions of source code must retain the above copyright notice,
+ this list of conditions and the following disclaimer.
+
+ 2. Redistributions in binary form must reproduce the above copyright
+ notice, this list of conditions and the following disclaimer in the
+ documentation and/or other materials provided with the distribution.
+
+ THIS SOFTWARE IS PROVIDED ``AS IS'' AND ANY EXPRESS OR IMPLIED WARRANTIES,
+ INCLUDING, BUT NOT LIMITED TO, THE IMPLIED WARRANTIES OF MERCHANTABILITY
+ AND FITNESS FOR A PARTICULAR PURPOSE ARE DISCLAIMED. IN NO EVENT SHALL THE
+ AUTHOR BE LIABLE FOR ANY DIRECT, INDIRECT, INCIDENTAL, SPECIAL, EXEMPLARY,
+ OR CONSEQUENTIAL DAMAGES (INCLUDING, BUT NOT LIMITED TO, PROCUREMENT OF
+ SUBSTITUTE GOODS OR SERVICES; LOSS OF USE, DATA, OR PROFITS; OR BUSINESS
+ INTERRUPTION) HOWEVER CAUSED AND ON ANY THEORY OF LIABILITY, WHETHER IN
+ CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE)
+ ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE
+ POSSIBILITY OF SUCH DAMAGE.
+
+*/
+
+// create apcupsd.conf
+$apcupsdconf=<<<EOF
+## apcupsd.conf v1.1 ##
+#
+# for apcupsd release 3.14.10 (13 September 2011) - freebsd
+#
+# "apcupsd" POSIX config file
+
+#
+# ========= General configuration parameters ============
+#
+
+# UPSNAME xxx
+# Use this to give your UPS a name in log files and such. This
+# is particulary useful if you have multiple UPSes. This does not
+# set the EEPROM. It should be 8 characters or less.
+UPSNAME {$upsname}
+
+# UPSCABLE <cable>
+# Defines the type of cable connecting the UPS to your computer.
+#
+# Possible generic choices for <cable> are:
+# simple, smart, ether, usb
+#
+# Or a specific cable model number may be used:
+# 940-0119A, 940-0127A, 940-0128A, 940-0020B,
+# 940-0020C, 940-0023A, 940-0024B, 940-0024C,
+# 940-1524C, 940-0024G, 940-0095A, 940-0095B,
+# 940-0095C, M-04-02-2000
+#
+UPSCABLE {$upscable}
+
+# To get apcupsd to work, in addition to defining the cable
+# above, you must also define a UPSTYPE, which corresponds to
+# the type of UPS you have (see the Description for more details).
+# You must also specify a DEVICE, sometimes referred to as a port.
+# For USB UPSes, please leave the DEVICE directive blank. For
+# other UPS types, you must specify an appropriate port or address.
+#
+# UPSTYPE DEVICE Description
+# apcsmart /dev/tty** Newer serial character device, appropriate for
+# SmartUPS models using a serial cable (not USB).
+#
+# usb <BLANK> Most new UPSes are USB. A blank DEVICE
+# setting enables autodetection, which is
+# the best choice for most installations.
+#
+# net hostname:port Network link to a master apcupsd through apcupsd's
+# Network Information Server. This is used if the
+# UPS powering your computer is connected to a
+# different computer for monitoring.
+#
+# snmp hostname:port:vendor:community
+# SNMP network link to an SNMP-enabled UPS device.
+# Hostname is the ip address or hostname of the UPS
+# on the network. Vendor can be can be "APC" or
+# "APC_NOTRAP". "APC_NOTRAP" will disable SNMP trap
+# catching; you usually want "APC". Port is usually
+# 161. Community is usually "private".
+#
+# netsnmp hostname:port:vendor:community
+# OBSOLETE
+# Same as SNMP above but requires use of the
+# net-snmp library. Unless you have a specific need
+# for this old driver, you should use 'snmp' instead.
+#
+# dumb /dev/tty** Old serial character device for use with
+# simple-signaling UPSes.
+#
+# pcnet ipaddr:username:passphrase:port
+# PowerChute Network Shutdown protocol which can be
+# used as an alternative to SNMP with the AP9617
+# family of smart slot cards. ipaddr is the IP
+# address of the UPS management card. username and
+# passphrase are the credentials for which the card
+# has been configured. port is the port number on
+# which to listen for messages from the UPS, normally
+# 3052. If this parameter is empty or missing, the
+# default of 3052 will be used.
+#
+UPSTYPE {$upstype}
+
+# POLLTIME <int>
+# Interval (in seconds) at which apcupsd polls the UPS for status. This
+# setting applies both to directly-attached UPSes (UPSTYPE apcsmart, usb,
+# dumb) and networked UPSes (UPSTYPE net, snmp). Lowering this setting
+# will improve apcupsd's responsiveness to certain events at the cost of
+# higher CPU utilization. The default of 60 is appropriate for most
+# situations.
+POLLTIME {$polltime}
+
+# LOCKFILE <path to lockfile>
+# Path for device lock file. Not used on Win32.
+LOCKFILE /var/spool/lock
+
+# SCRIPTDIR <path to script directory>
+# Directory in which apccontrol and event scripts are located.
+SCRIPTDIR /usr/local/etc/apcupsd
+
+# PWRFAILDIR <path to powerfail directory>
+# Directory in which to write the powerfail flag file. This file
+# is created when apcupsd initiates a system shutdown and is
+# checked in the OS halt scripts to determine if a killpower
+# (turning off UPS output power) is required.
+PWRFAILDIR /var/run
+
+# NOLOGINDIR <path to nologin directory>
+# Directory in which to write the nologin file. The existence
+# of this flag file tells the OS to disallow new logins.
+NOLOGINDIR /var/run
+
+
+#
+# ======== Configuration parameters used during power failures ==========
+#
+
+# The ONBATTERYDELAY is the time in seconds from when a power failure
+# is detected until we react to it with an onbattery event.
+#
+# This means that, apccontrol will be called with the powerout argument
+# immediately when a power failure is detected. However, the
+# onbattery argument is passed to apccontrol only after the
+# ONBATTERYDELAY time. If you don't want to be annoyed by short
+# powerfailures, make sure that apccontrol powerout does nothing
+# i.e. comment out the wall.
+ONBATTERYDELAY {$onbatterydelay}
+
+#
+# Note: BATTERYLEVEL, MINUTES, and TIMEOUT work in conjunction, so
+# the first that occurs will cause the initation of a shutdown.
+#
+
+# If during a power failure, the remaining battery percentage
+# (as reported by the UPS) is below or equal to BATTERYLEVEL,
+# apcupsd will initiate a system shutdown.
+BATTERYLEVEL {$batterylevel}
+
+# If during a power failure, the remaining runtime in minutes
+# (as calculated internally by the UPS) is below or equal to MINUTES,
+# apcupsd, will initiate a system shutdown.
+MINUTES {$minutes}
+
+# If during a power failure, the UPS has run on batteries for TIMEOUT
+# many seconds or longer, apcupsd will initiate a system shutdown.
+# A value of 0 disables this timer.
+#
+# Note, if you have a Smart UPS, you will most likely want to disable
+# this timer by setting it to zero. That way, you UPS will continue
+# on batteries until either the % charge remaing drops to or below BATTERYLEVEL,
+# or the remaining battery runtime drops to or below MINUTES. Of course,
+# if you are testing, setting this to 60 causes a quick system shutdown
+# if you pull the power plug.
+# If you have an older dumb UPS, you will want to set this to less than
+# the time you know you can run on batteries.
+TIMEOUT {$timeout}
+
+# Time in seconds between annoying users to signoff prior to
+# system shutdown. 0 disables.
+ANNOY {$annoy}
+
+# Initial delay after power failure before warning users to get
+# off the system.
+ANNOYDELAY {$annoydelay}
+
+# The condition which determines when users are prevented from
+# logging in during a power failure.
+# NOLOGON <string> [ disable | timeout | percent | minutes | always ]
+NOLOGON disable
+
+# If KILLDELAY is non-zero, apcupsd will continue running after a
+# shutdown has been requested, and after the specified time in
+# seconds attempt to kill the power. This is for use on systems
+# where apcupsd cannot regain control after a shutdown.
+# KILLDELAY <seconds> 0 disables
+KILLDELAY {$killdelay}
+
+#
+# ==== Configuration statements for Network Information Server ====
+#
+
+# NETSERVER [ on | off ] on enables, off disables the network
+# information server. If netstatus is on, a network information
+# server process will be started for serving the STATUS and
+# EVENT data over the network (used by CGI programs).
+NETSERVER {$netserver}
+
+# NISIP <dotted notation ip address>
+# IP address on which NIS server will listen for incoming connections.
+# This is useful if your server is multi-homed (has more than one
+# network interface and IP address). Default value is 0.0.0.0 which
+# means any incoming request will be serviced. Alternatively, you can
+# configure this setting to any specific IP address of your server and
+# NIS will listen for connections only on that interface. Use the
+# loopback address (127.0.0.1) to accept connections only from the
+# local machine.
+NISIP ${nisip}
+
+# NISPORT <port> default is 3551 as registered with the IANA
+# port to use for sending STATUS and EVENTS data over the network.
+# It is not used unless NETSERVER is on. If you change this port,
+# you will need to change the corresponding value in the cgi directory
+# and rebuild the cgi programs.
+NISPORT ${nisport}
+
+# If you want the last few EVENTS to be available over the network
+# by the network information server, you must define an EVENTSFILE.
+EVENTSFILE /var/log/apcupsd.events
+
+# EVENTSFILEMAX <kilobytes>
+# By default, the size of the EVENTSFILE will be not be allowed to exceed
+# 10 kilobytes. When the file grows beyond this limit, older EVENTS will
+# be removed from the beginning of the file (first in first out). The
+# parameter EVENTSFILEMAX can be set to a different kilobyte value, or set
+# to zero to allow the EVENTSFILE to grow without limit.
+EVENTSFILEMAX 10
+
+#
+# ========== Configuration statements used if sharing =============
+# a UPS with more than one machine
+
+#
+# Remaining items are for ShareUPS (APC expansion card) ONLY
+#
+
+# UPSCLASS [ standalone | shareslave | sharemaster ]
+# Normally standalone unless you share an UPS using an APC ShareUPS
+# card.
+UPSCLASS {$upsclass}
+
+# UPSMODE [ disable | share ]
+# Normally disable unless you share an UPS using an APC ShareUPS card.
+UPSMODE {$upsmode}
+
+#
+# ===== Configuration statements to control apcupsd system logging ========
+#
+
+# Time interval in seconds between writing the STATUS file; 0 disables
+STATTIME 0
+
+# Location of STATUS file (written to only if STATTIME is non-zero)
+STATFILE /var/log/apcupsd.status
+
+# LOGSTATS [ on | off ] on enables, off disables
+# Note! This generates a lot of output, so if
+# you turn this on, be sure that the
+# file defined in syslog.conf for LOG_NOTICE is a named pipe.
+# You probably do not want this on.
+LOGSTATS off
+
+# Time interval in seconds between writing the DATA records to
+# the log file. 0 disables.
+DATATIME 0
+
+# FACILITY defines the logging facility (class) for logging to syslog.
+# If not specified, it defaults to "daemon". This is useful
+# if you want to separate the data logged by apcupsd from other
+# programs.
+#FACILITY DAEMON
+
+#
+# ========== Configuration statements used in updating the UPS EPROM =========
+#
+
+#
+# These statements are used only by apctest when choosing "Set EEPROM with conf
+# file values" from the EEPROM menu. THESE STATEMENTS HAVE NO EFFECT ON APCUPSD.
+#
+
+# UPS name, max 8 characters
+#UPSNAME UPS_IDEN
+
+# Battery date - 8 characters
+#BATTDATE mm/dd/yy
+
+# Sensitivity to line voltage quality (H cause faster transfer to batteries)
+# SENSITIVITY H M L (default = H)
+#SENSITIVITY H
+
+# UPS delay after power return (seconds)
+# WAKEUP 000 060 180 300 (default = 0)
+#WAKEUP 60
+
+# UPS Grace period after request to power off (seconds)
+# SLEEP 020 180 300 600 (default = 20)
+#SLEEP 180
+
+# Low line voltage causing transfer to batteries
+# The permitted values depend on your model as defined by last letter
+# of FIRMWARE or APCMODEL. Some representative values are:
+# D 106 103 100 097
+# M 177 172 168 182
+# A 092 090 088 086
+# I 208 204 200 196 (default = 0 => not valid)
+#LOTRANSFER 208
+
+# High line voltage causing transfer to batteries
+# The permitted values depend on your model as defined by last letter
+# of FIRMWARE or APCMODEL. Some representative values are:
+# D 127 130 133 136
+# M 229 234 239 224
+# A 108 110 112 114
+# I 253 257 261 265 (default = 0 => not valid)
+#HITRANSFER 253
+
+# Battery charge needed to restore power
+# RETURNCHARGE 00 15 50 90 (default = 15)
+#RETURNCHARGE 15
+
+# Alarm delay
+# 0 = zero delay after pwr fail, T = power fail + 30 sec, L = low battery, N = never
+# BEEPSTATE 0 T L N (default = 0)
+#BEEPSTATE T
+
+# Low battery warning delay in minutes
+# LOWBATT 02 05 07 10 (default = 02)
+#LOWBATT 2
+
+# UPS Output voltage when running on batteries
+# The permitted values depend on your model as defined by last letter
+# of FIRMWARE or APCMODEL. Some representative values are:
+# D 115
+# M 208
+# A 100
+# I 230 240 220 225 (default = 0 => not valid)
+#OUTPUTVOLTS 230
+
+# Self test interval in hours 336=2 weeks, 168=1 week, ON=at power on
+# SELFTEST 336 168 ON OFF (default = 336)
+#SELFTEST 336
+EOF;
+?>